| 23 36 00 Air Terminal Units | SDV Single-Duct VAV Terminal Unit with 2-Row Hot Water Reheat Price Industries · SDV-08-RH2-F1 Pressure-independent single-duct variable air volume (VAV) terminal unit featuring multi-point SP300 airflow sensor, low-leakage heavy-gauge casing, and factory-mounted 2-row hydronic reheat coil. | AHRI Standard 880 Certified PerformanceUL 181 Erosion & Mold Growth Resistant LinerNFPA 90A Flame/Smoke 25/50 RatedASHRAE Standard 130 Air Terminal Testing | - Inlet Size / Airflow: 8 in round inlet · 140 to 900 CFM nominal operating range
- Casing Construction: 22-gauge galvanized steel, mechanically locked low-leakage seams
- Damper Assembly: Double-thickness 22-ga steel blade with closed-cell foam seal (<2% leakage)
| Load Item |
| 23 34 23 HVAC Power Ventilators | Model GB-141 Belt-Drive Centrifugal Roof Exhaust Fan Greenheck · GB-141-4-QD-X Spun-aluminum downblast centrifugal roof exhaust ventilator with non-overloading backward-inclined wheel, vibration-isolated drive frame, and factory NEMA 3R disconnect switch. | AMCA 210 Air Performance CertifiedAMCA 300 Sound Performance CertifiedUL / cUL 705 Power Ventilators ListedMiami-Dade / IBC High-Wind Curb Rated | - Design Performance: 2,150 CFM @ 0.625 in w.g. static pressure, 1,180 RPM
- Motor & Electrical: 1/2 HP, 208-230/460V 3-phase 60Hz ODP, NEMA Premium Eff.
- Sound Rating: 10.8 Sones at 5 ft free-field hemispherical inlet
| Load Item |
| 23 74 13 Packaged, Outdoor, Central-Station Air-Handling Units | Precedent 10-Ton Packaged Rooftop Unit (Gas/Electric) Trane · YSC120H4RHA-10T Commercial 10-ton standard-efficiency packaged rooftop unit with dual-stage scroll compressors, direct-drive plenum ECM supply fan, low-leakage economizer, and Symbio 700 BACnet controller. | AHRI Standard 340/360 CertifiedASHRAE 90.1 Energy Efficiency CompliantUL 60335-2-40 Listed (A2L R-454B Safety)ANSI Z21.47 Gas-Fired Central Furnace | - Cooling Capacity: 118,000 Btu/h gross (10 Nominal Tons) · 14.8 IEER / 11.2 EER
- Heating Section: 205,000 Btu/h input stainless steel tubular heat exchanger (81% AFUE)
- Refrigerant Circuit: Dual independent R-454B circuits with factory A2L leak mitigation sensor
| Load Item |
| 23 37 13 Diffusers, Registers, and Grilles | OMNI Architectural Plaque Ceiling Supply Diffuser Titus HVAC · OMNI-AA-24x24-10IN Architectural flush-face steel/aluminum plaque ceiling diffuser engineered for uniform 360-degree radial Coanda airflow in open offices, clinical exam rooms, and VAV zones. | ASHRAE Standard 70 Air Outlet TestingADC 1062:GRD-84 Certified PerformanceASTM B209 Architectural Aluminum FaceISO 5219 Air Distribution Aerodynamic Test | - Module & Neck Size: 24 in x 24 in lay-in T-bar module with 10 in round inlet neck
- Design Airflow: 350 CFM nominal · Throw 9-13-18 ft (150-100-50 fpm terminal)
- Pressure & Sound: 0.085 in w.g. total pressure drop · NC 21 acoustic rating
| Load Item |
| 23 07 13 Duct Insulation | SOFTR Duct Wrap FRK Foil-Reinforced Kraft Blanket Owens Corning · SOFTR-FRK-2IN-R6 Flexible formaldehydefree fiberglass blanket insulation factory-laminated to a vapor-retarding FRK (foil-reinforced kraft) facing for exterior thermal and condensation control on HVAC ductwork. | ASTM C1290 Type III Flexible Fibrous BlanketASTM E84 Flame Spread <= 25 / Smoke <= 50NFPA 90A & NFPA 90B HVAC Duct ComplianceUL GREENGUARD Gold Indoor Air Quality | - Thickness & Density: 2.2 in nominal (1.65 in installed at 25% max compression), 0.75 pcf
- Installed R-Value: R-6.0 hr*ft2*F/Btu at 75 F mean temperature (ASTM C518)
- Vapor Retarder Facing: FRK reinforced aluminum foil/kraft with 2 in stapling/taping flange
| Load Item |
| 23 09 23 Direct-Digital Control System for HVAC | LMB24-SR Proportional Non-Spring-Return Damper Actuator Belimo · LMB24-SR-45INLB Direct-coupled 24V AC/DC modulating brushless DC damper actuator delivering 45 in-lb torque with 2–10V DC proportional control, feedback output, and electronic overload protection. | UL 60730-1 / UL 60730-2-14 RecognizedCSA C22.2 No. 24 CertifiedNEMA 2 / IP54 Enclosure ProtectionISO 9001 Quality Management Certified | - Torque Output: 45 in-lb (5 Nm) minimum constant torque across full 95 deg stroke
- Power Supply: 24 VAC +/-20% 50/60 Hz or 24 VDC +/-10% (1.5W running / 0.4W hold)
- Control Signal: 2 to 10 VDC modulating input (0–10V / 4–20mA with 500-ohm resistor)